WOOD — Floors, Interior - Ceramic or Porcelain Tile 5
19.2" (488 mm) o.c. joist spacing, single layer OSB
or plywood subfloor
DH-W19-T-15
Areas of Application
over any even and structurally sound OSB or
plywood subfloor with 19.2" (488 mm) o.c.
joist spacing
interior dry or wet areas
Limitations
minimum 2" x 2" (50 mm x 50 mm) tile
for natural stone, see detail DH-W-S (page 6)
and natural stone discussion (page 23)
Requirements
maximum spacing of joists, I-joists, or floor
trusses is 19.2" (488 mm) o.c.
minimum subfloor thickness – 23/32",
3/4" nom. (19 mm) tongue-and-groove with
1/8" (3 mm) gap between sheets.
Substrate Preparation
verify that subfloor panels are properly
fastened to framing members.
any leveling of the subfloor must be done
prior to installing DITRA-HEAT.
Movement Joints
DITRA-HEAT does not eliminate the need for
movement joints, including perimeter joints,
within the tiled surface. Movement joints
must be installed in accordance with industry
standards and norms; see page 11 of this
Handbook, TCNA EJ171, and TTMAC 301 MJ.
Setting and Grouting Materials
latex portland cement (p.c.) mortar –
ANSI A118.11
unmodified thin-set mortar – ANSI A118.1
grout – ANSI A118.3, A118.6, A118.7, A118.8
Setting and Grouting Specifications
tile – ANSI A108.5
grout – ANSI A108.6, A108.9, A108.10
Other Considerations
tightly butted and/or tented plywood or OSB
seams must be addressed prior to installing
DITRA-HEAT.
vapor barrier on crawl space floors according
to regional building codes.
where a waterproof floor is required, all
DITRA-HEAT seams and floor/wall transitions
must be sealed with KERDI-BAND using
unmodified thin-set mortar; see page 10.
DH-W24-T-15
24" (610 mm) o.c. joist spacing, double layer OSB
or plywood subfloor
Areas of Application
over any even and structurally sound double
layer OSB or plywood floor
interior dry or wet areas
Limitations
minimum 2" x 2" (50 mm x 50 mm) tile
Requirements
maximum spacing of joists, I-joists, or floor
trusses is 24" (610 mm) o.c.
double layer wood floor consisting of:
minimum subfloor thickness – 23/32",
3/4" nom. (19 mm) tongue-and-groove
minimum underlayment thickness –
11/32", 3/8" nom. (10 mm)
Substrate preparation
verify that subfloor panels are properly
fastened to framing members.
underlayment – minimum 11/32", 3/8" nom.
(10 mm)-thick Exposure 1, plugged-face
plywood or OSB with 1/8" (3 mm) gap
between sheets; see page 14 for
underlayment installation guidelines.
any leveling of the subfloor must be done
prior to installing DITRA-HEAT.
Movement Joints
DITRA-HEAT does not eliminate the need for
movement joints, including perimeter joints,
within the tiled surface. Movement joints must
be installed in accordance with industry
standards and norms; see page 11 of this
Handbook, TCNA EJ171, and TTMAC 301 MJ.
Setting and Grouting Materials
latex portland cement (p.c.) mortar –
ANSI A118.11
unmodified thin-set mortar – ANSI A118.1
grout – ANSI A118.3, A118.6, A118.7, A118.8
Setting and Grouting Specifications
tile – ANSI A108.5
grout – ANSI A108.6, A108.9, A108.10
Other Considerations
tightly butted and/or tented plywood or OSB
seams must be addressed prior to installing
DITRA-HEAT.
vapor barrier on crawl space floors according
to regional building codes.
where a waterproof floor is required, all
DITRA-HEAT seams and floor/wall transitions
must be sealed with KERDI-BAND using
unmodified thin-set mortar; see page 10.
Ceramic or porcelain tile
Unmodified thin-set mortar
DITRA-HEAT
uncoupling membrane
and heating cables
Latex p.c. mortar
Double layer of plywood
or OSB
I-joists or
trusses
Ceramic or porcelain tile
Unmodified thin-set mortar
DITRA-HEAT
uncoupling membrane
and heating cables
Latex p.c. mortar
Single layer of plywood
or OSB
Joists, I-joists, or
trusses